Can SoMachine controller communicate to a HMI program with Vijeo XD V3.0
Issue:
How do I setup communication between the Controller and HMI and link the variables.
Product Line:
M238, M241, M251, M258
HMIGTO, HMIG3U
Environment:
SoMachine V4.3
Vijeo XD 3.0
Resolution:
Vijeo XD V3.0 is not integrated with SoMachine V4.3
You have to create a separate SoMachine application for the M251 controller and a separate Vijeo XD V3.0 application for the Magelis HMI.
In Vijeo XD, use the SoMachine Network driver under Schneider Electric. Copy the Node name from the SoMachine application.
Create a symbol link and browse for the application name XML file to import the tags from SoMachine to Vijeo XD. This file is created during a download in SoMachine.
How do I setup communication between the Controller and HMI and link the variables.
Product Line:
M238, M241, M251, M258
HMIGTO, HMIG3U
Environment:
SoMachine V4.3
Vijeo XD 3.0
Resolution:
Vijeo XD V3.0 is not integrated with SoMachine V4.3
You have to create a separate SoMachine application for the M251 controller and a separate Vijeo XD V3.0 application for the Magelis HMI.
In Vijeo XD, use the SoMachine Network driver under Schneider Electric. Copy the Node name from the SoMachine application.
Create a symbol link and browse for the application name XML file to import the tags from SoMachine to Vijeo XD. This file is created during a download in SoMachine.
Released for: Schneider Electric UK
Explore more
Range:
Explore more
Range:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Centre
Find support resources for all your needs, in one place.