How to access fault current shall be available on Default display on P132?

These values are available but you need to configure the same :
Config. parameters-> LOC-> Fct. fault Panel-> Fault Curr.P. Pu & Fault Curr.N. Pu.
But we recommend to use the disturbance recorder file if someone really wants analysis.

Fault current is available in Events->measured fault data->FT_DA->Fault curr. N p.u.

In Events> Measure Fault Data> FT_DA- Fault current and type of fault is available & it is the last recent fault data is available here.