How can we help you today?
How do I program the ATV61 analog output for an 0-10Vdc feedback?
Issue:
Program the ATV61 analog output for an 0-10Vdc feedback .
Product Line:
ATV61 / ATV71
Environment:
All serial numbers
Cause:
Need feedback signal
Resolution:
Main menu > Drive > Input / output menu > Set AO1 type to "IOU". Set UOL1 to 0 and UOH1 to 10.
Program the ATV61 analog output for an 0-10Vdc feedback .
Product Line:
ATV61 / ATV71
Environment:
All serial numbers
Cause:
Need feedback signal
Resolution:
Main menu > Drive > Input / output menu > Set AO1 type to "IOU". Set UOL1 to 0 and UOH1 to 10.
Released for: Schneider Electric UK
Explore more
Range:
Explore more
Range:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Centre
Find support resources for all your needs, in one place.