{}

Our Brands

Impact-Company-Logo-English Black-01-177x54

Welcome to the Schneider Electric Website

Welcome to our website.

Search FAQs

Altivar Process ATV600 and Speed error in Profidrive ZSW1.8 when controlling drive on Profinet

The speed error (also known as velocity error) is the difference between the target speed setpoint and actual speed. If this value exceeds the speed error tolerance while controlling speed PID, the bit will signalize out of tolerance range.
The tolerance range cannot be set by a simple parameter. The tolerance range depends on speed loop setting (proportional gain, integral time).
This speed error bit exists on profinet/profidrive only. For other communications, ETA does not have this bit.

Schneider Electric UK

Explore more
Explore more
Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.