What demand parameters are available in PM1130H meter ?
Issue:
Need to identify the demand values, demand calculation methods, and available demand measurements supported by the PM1130H meter.
Product Line:
PM1130H meter
Environment:
Viewing demand information locally on the meter and/or through communications
Monitoring applications where demand history, peak tracking, and demand calculation method selection are required
Cause:
Demand reporting varies by device. Users need to know which demand values, peak timestamping, calculation methods, and reset options are available on the PM1130H.
Resolution:
The PM1130H provides the following demand-related parameters and functions:
- Demand values available:
- Last demand
- Present demand
- Maximum (Peak) demand
- Timestamp via counters indicating when the maximum (peak) demand occurred
- Supported demand calculation methods:
- Sliding block
- Fixed block
- Rolling block
- Peak demand reset options:
- Manual reset (password protected)
- Reset through communication
- Demand measurements include (Total):
- W (Demand)
- VAR (Demand)
- VA (Demand)
Released for: Schneider Electric UK