Our Brands

Welcome to the Schneider Electric Website

Welcome to our website.
		
How can we help you today?
Freq. inverter ATV Process on Profinet network. How read/write more than 8 PZDs? The SoMove Eth/IP scanner displays the max of 8
YEs, it is possible to map up to 16 input and 16 output PZDs on profinet, profile 107. Somove does not show profinet mapping variables. Variables have to be mapped in PLC profinet configuration.
Eth/IP scanner shows mapping for eth/ip communication, but if you use profinet, then whatever variables are seen in ethernet IP scanner they are irrelevant. Somove shows a kind of default scanner prepared for eth IP.
Tested in TIA portal v 15, S7-1500, ATV930.

Schneider Electric UK

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and contact centre
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings