How can we help you today?

How do you wire an 8903L electrically held lighting contactor to a 3-wire photocell control?

Issue:
Wiring a 3-wire Photocell to an 8903L electrically held contactor

Product Line:
Lighting contactor

Environment:
8903 Type L electrically held

Resolution:
Most standard photocells have 3 wires.   Black is supply voltage, L1.  White is neutral or L2.  Red is the switched leg.   Run the switched leg to one side of the coil and the other side of the coil to the neutral or L2.   See attached diagram.

Schneider Electric UK

Explore more

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more

Explore more

Need help?

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Start your sales inquiry online and an expert will connect with you.

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Centre

Find support resources for all your needs, in one place.