How can we help you today?
How can it be verified the motor is running through the shorting contactor and not the ATS48?
Issue:
Validate motor is running through the shorting contactor, not the soft starter.
Product Line:
ATS48
Environment:
All serial numbers
Cause:
Testing the contactor
Resolution:
Verify the r2A and r2C is closed.
Measure motor current on the load side of the shorting contactor.
Validate motor is running through the shorting contactor, not the soft starter.
Product Line:
ATS48
Environment:
All serial numbers
Cause:
Testing the contactor
Resolution:
Verify the r2A and r2C is closed.
Measure motor current on the load side of the shorting contactor.
Released for: Schneider Electric UK
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Centre
Find support resources for all your needs, in one place.