Our Brands

Welcome to the Schneider Electric Website

Welcome to our website.
		
How can we help you today?
Can I use a standard 0-10Vdc input on a bipolar (+10)/(-10Vdc) input?
Issue:
Using a standard 0-10Vdc input on a bipolar input

Product Line:
ATV31, ATV312, ATV61, ATV71,

Environment:
All series

Cause:
At 5Vdc the drive ramps to full speed.

Resolution:
Must use a bipolar signal to get the proper scaling and reference.
Bipolar analog input 0 ± 10 V (max. safe voltage ± 30 V)
The + or - polarity of the voltage on AI2 affects the direction of the setpoint
and therefore the direction of operation.

Schneider Electric UK

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and contact centre
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings