How can we help you today?

EF SHR unexpected behavior

You are using Unity Pro V11 or higher and option Optimized code is selected (Project Settings / Build settings / Optimized code)
You are using M580 High End CPU, BMEP585040, BMEP586040 or BMEH586040.
In such configuration because these CPU used a new compilator managing differently data signed and data unsigned the result of the EF operation is unexpected.

A workaround exists, use the EF SHR_INT or use only UINT data type when using a SHR. A comment will be added on the Unity Pro Read_Me.

NOTA This behavior doesn’t exist with other M580 PLCs references.

Schneider Electric UK

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and contact centre
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • General Terms of Business
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings
  • Preference Center