What is CVT calibration data?
Issue
User wants to know what CVT calibration data is.
Product
N, U, W, RL Series Reclosers
Environment
WSOS5
Cause
Voltage measurement accuracy in these recloser systems depends on device‑specific calibration values determined during factory testing.
Resolution
CVT calibration data is one of the key variables used by the voltage‑measurement algorithm in the recloser control system. These data values are:
- Determined during final routine factory tests.
- Stored in the SCEM board for the N, U, W, and RL series reclosers.
- Stored inside the ADVC3 controller for E‑series devices (paired during factory CVT calibration).
Because of natural manufacturing tolerances in electronic components and bushings, each bushing and SCEM combination has unique CVT calibration data.
Impact of SCEM Replacement
For N, U, W, and RL series reclosers, replacing the SCEM board may cause incorrect voltage readings.
To correct this:
- Reload the latest CVT calibration data file into the device.
- Use the Calibration menu in WSOS5 to fine‑tune voltage measurement.
- Follow the on‑site CVT Calibration procedure for detailed steps.
Proper loading and calibration ensure accurate voltage measurement after hardware replacement.
Released for: Schneider Electric UK
Explore more
Range:
Explore more
Range:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Centre
Find support resources for all your needs, in one place.