Our Brands

Welcome to the Schneider Electric Website

Welcome to our website.
		
How can we help you today?
What is LSC2B defined in IEC 62271-200?

LSC2B is defined in IEC 62271-200 standard as the loss of Service Continuity category.


Medium voltage parts are compartmented and separated using metal partitions (PM class) which are connected to the earth.

  • Busbars compartment
  • Compartment for switching device (withdrawable part - circuit breaker, fuse-contactor, disconnector truck or earthing truck)
  • MV cables connection compartment (earthing switch, current sensors, voltage transformers)

LSC category provides a guarantee that there is a high level of people protection; when a compartment containing a main circuit is open, the other compartments and/or functional units may remain energized.

MCset and PIX switch gears are the LSC category of LSC2B.


Switchgear panel construction is with metal partition walls and isolating distances with compartmentalization to the busbar and to the cable.

Schneider Electric UK

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and contact centre
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings