Why is Unity OSLoader showing remote device as ETY410?
Title
Unity OSLoader showing remote device as ETY410

Issue
Unity OSLoader showing wrong remote device

Product Line
Unity OSLoader

Environment
Unity Pro

Resolution
When Unity OSLoader identifies a 140CRP31200 or any other device as an ETY410, that means your FTP connection was not getting established or blocked.
Please turn off your PC's anti-virus, firewall and/or wireless adapter, so that the OSLoader FTP connection is able to be established.