Our Brands

Welcome to the Schneider Electric Website

Welcome to our website.
		
How can we help you today?
What resistance we could connect to terminals of LT3S* Thermistor relay in order to simulate a connected PTC probe?
The significant resistance is in range 1500...3100 Ohm (trip zone, reset zone) - see Attachment1.

Schneider Electric UK

Attachment(s)
Attachment1.pdf [148.95 KB]
Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and contact centre
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings