Can Remote Control be enabled from the advanced UMI of the Sepam Series 20, 40 and 80 Relay?

For the Sepam Series 20 and 40 relay.

"Remote Control" can be activated by navigating through the front face of the Sepam relay.
Go to general settings -> Modules -> Modbus. Scroll down until the remote control screen appears
Sepam 20, 40 relay front face, Modbus

Note: "SBO" means Select Before Operate

For the Sepam Series 80 relay

"Remote Control" can not be activated by navigating through the front of the relay.
In order to activate this setting, connect to the relay using the SFT2841 Software kit with the CCA783 cord.
"Remote Settings" is located under the "General Characteristics" tab of SFT2841.

SFT2841 Sepam Characteristics tab to enable Remote settings