How can we help you today?
When powering multiple ATV930 drives straight to the DC bus with a common DC power supply, what parameters need to be adjusted?
Issue:
Parameters to adjust when powering multiple ATV930 drives straight to the DC bus with a common DC power supply.
Product Line:
Altivar 930
Environment:
All
Cause:
Powering ATV930's with a single common DC power supply
Resolution:
1. Set your Access Level to Expert:
2. Set DC Bus Source Type to Supply Unit REC:
Parameters to adjust when powering multiple ATV930 drives straight to the DC bus with a common DC power supply.
Product Line:
Altivar 930
Environment:
All
Cause:
Powering ATV930's with a single common DC power supply
Resolution:
1. Set your Access Level to Expert:
- [My Preferences] -> [Access Level] -> [Expert]
2. Set DC Bus Source Type to Supply Unit REC:
- [Complete settings] -> [Generic functions] ->[dbS] ->[dCbS] ->[Supply Unit REC]
Released for: Schneider Electric UK
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Centre
Find support resources for all your needs, in one place.