How can we help you today?
How to check power fan functionality on ATV630C16N4?
If power fan never rotates when ATV is in operation, the fan should be removed and tested first mechanically by hand to exclude bearing malfunction, then electrical test using external 48V DC.
Attached picture shows cable that connects fan with X22 connector on power board.
Pin 1 and 2 on X22 provides 48V DC for the fan (pin1 +, pin2 -). Pin 3 is dedicated for fan feedback.
Attached picture shows cable that connects fan with X22 connector on power board.
Pin 1 and 2 on X22 provides 48V DC for the fan (pin1 +, pin2 -). Pin 3 is dedicated for fan feedback.
Released for: Schneider Electric UK
Attachment(s)
Explore more
Range:
Explore more
Range:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Centre
Find support resources for all your needs, in one place.