Our Brands

Welcome to the Schneider Electric Website

Welcome to our website.
		
How can we help you today?
For BMEAHI0812 and BMEAHO0412 the "isolation“ between channels = 1000 VDC". Why don't we deliver a value in AC voltage ?
For BMEAHI0812 and BMEAHO0412 the „isolation“ between channels 1000 VDC (1 minute duration)", between channels and bus 1400 VDC(1 minute duration), between channels and ground 1400 VDC (1 minute duration). The question is if these values are also valid for AC voltage? Or whats are the values for AC voltage?

=> Concerning the strength of the isolation barrier, normally the AC level = (DC level / 1.414). But the real test is not allowed to be done in AC way for this case due to the existence of Y-capacitor or parasite capacitor. So the norm allows to choose DC test only and it will not impact the judgement to the strength of isolation barrier.

Schneider Electric UK

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and contact centre
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings