Our Brands

Welcome to the Schneider Electric Website

Welcome to our website.
		
How can we help you today?
ROHS for ILP stepper motors?
YEs, declaration about conformity with ROHS is in attachment.

Schneider Electric UK

Attachment(s)
CERTIFICATE OF CONFORMANCE.pdf [193.41 KB]
Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and contact centre
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings