Our Brands

Welcome to the Schneider Electric Website

Welcome to our website.
		
How can we help you today?
Can SoMove Software be used to monitor multiple drives over a Modbus network?
Issue:
Can SoMove Software be used to monitor multiple drives over a Modbus network?

Product Line:
Altivar Process Drive

Environment:
All models and serial numbers

Cause:
Wiring / Programming

Resolution:
You can use the resident Modbus RTU on the drive so no Gateway is required.  You would configure each drive with a Modbus Network address.  Cable used to daisychain  (VW3A8306TF03 or ..F10) via Modbus.
The cable is F03=.3 M or 1ft, or 10= 1.0M or 3ft.   Set the Scan up as Multipoint, and have to setup the range of registers.

Schneider Electric UK

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and contact centre
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings