What information is saved in the event of a Sepam series 80 power failure?

The saving of information depends on whether or not the battery is present. In the event of a Sepam series 80 power failure, certain data will only be saved if the battery is present.

The data listed below are only saved if the battery is present:

  • Peak demand current
  • Peak demand active power
  • Peak demand reactive power
  • Tripping context
  • Tripping current
  • Disturbance recordings
  • Starting current
  • Starting time
  • Alarm message history
  • Date and time


The data listed below are saved with or without a battery present:

  • Calculated active energy
  • Calculated reactive energy
  • Number of trips (phase overcurrent and earth fault)
  • Machine heat rise
  • Running hours counter and operating time
  • Cumulative breaking current
  • Number of operations
  • Operating time
  • Charging time
  • Number of rackouts


Important: all the data contained are saved in cartridge.

Schneider Electric UK

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and contact centre
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings