How do you change the M221 so that it runs as soon as it is powered ?
By default the software configure the controller to be "Start in Previous State", however this value can be changed:
There are four possible states for the Starting Mode parameter:
- Start In Previous State : The logic controller starts in the state that it was in before it was stopped
- Start in Stop : The logic controller does not automatically start application execution
- Start in Run : The logic controller automatically starts application execution given run criteria, such as the presence and charge of a battery, are met.
- Unconditional start in Run : The logic controller automatically starts application execution even if the controller battery is absent or discharged.
The video below shows how the SoMachine basic (Now known as EcoStruxure Machine Expert Basic ) program is configured and loaded in to the M221 Controller