How do I resolve the build message "C0106: Out of global data memory" in SoMachine / EcoStruxure Machine Expert Logic Builder?

Article available in these languages:

Issue
When attempting to Download or Code Generate my PLC Application in SoMachine or EcoStruxure Machine Expert Logic Builder,  the build message "C0106: Out of global data memory" appears in the Messages zone.

Product Line
SoMachine / EcoStruxure Machine Expert

Environment
Logic Builder PLC Configuration software in Windows

Cause
The build message "C0106: Out of global data memory" is caused by the application having more variables used in the Persistent Retain memory than there is physical memory on the PLC.

Resolution
Reduce the number of variables declared in the PersistentVars Application object or declared as "VAR_GLOBAL PERSISTENT RETAIN" in the Global Variable List (GVL) node.
Do this incrementally and go to the Build menu and perform the following actions in sequence:

  1. Clean
  2. Build
  3. Generate Code


After each Generate Code, check the Message list to see if the C0106 message has disappeared.

If so, one can see the used memory in the message list in the form of "Memory area 5 contains Persistent Data:…"
For example in Screenshot 2 below, 2044bytes is the maximum for the HMISCU PLC - of which 46% is used.

Tip: Watch for ARRAYs, DUT (structures) and combinations of the two (ARRAYs of DUTs), which can increase the defined memory usage multiplicatively.

To see how many bytes the PLC has allocated to the Persistent Retain Variables area, go to the SoMachine Online Help [PLC type section] -> Programming Guide -> Memory Mapping section

If this FAQ did not solve your issue, you can chat with us at chat with us or e-mail us at customer.services@se.com to create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance:

Support | Schneider Electric Global (se.com)

Schneider Electric UK

Attachment(s)

  • [64.78 KB]
  • [72.99 KB]

Explore more

Range:

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more

Explore more

Range:

Need help?

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Start your sales inquiry online and an expert will connect with you.

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Centre

Find support resources for all your needs, in one place.