Our Brands

Welcome to the Schneider Electric Website

Welcome to our website.
		
How can we help you today?
What can cause a LCF (Line contactor failure) on the Altivar Process Drive ATV630 and ATV930?
Issue:
What is the fault code LCF on the ATV630 and ATV930 drives?

Product Line:
ATV630  ATV930

Environment:
All serial numbers

Cause:
Customer said the drive had a fault code LCF.

Resolution:
The fault takes place as soon as the line contactor is not closed after a defined time (LCT).
This function allows the line contactor to close and open depending on the start/stop command.
Check the line contactor and its' wiring.
Check parameter LCT (Mains Voltage.time out) under Complete setting -> Generic functions -> Mains contactor comm -> Mains V. time out.
If there is a timing issue, try to increase this value.
The Mains Voltage time out is factory set to 5s.

Schneider Electric UK

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and contact centre
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings