Our Brands

Welcome to the Schneider Electric Website

Welcome to our website.
		
How can we help you today?
ATV660: Using the VW3A3203 for a Thermal Sensor

Article available in these languages: Spanish

Issue:
Set up AI4 for a Thermal Sensor using VW3A3203.

Product Line:
ATV660

Environment:
Thermal Sensor

Cause:
n/a

Resolution:
Response from France:
VW3A3203 card accepts standard Pt100 sensors for the range -20…+200 C deg
The temperature value is given at: TH4V (AI4 thermal value, @13252, unit: 0.1Cdeg )
The following settings are necessary:
AI4T = Pt100 in 3 wires (AI4 type)
TH4S = Yes (Activation of the thermal monitoring on AI4. )
You do not need to adjust any other parameters.

Schneider Electric UK

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and contact centre
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings