How can we help you today?
Where do you wire in remote speed reference to an ATV660?
Issue:
Wiring remote speed reference for an ATV660.
Product Line:
ATV660
Environment:
ALL
Cause:
Wiring / Programming
Resolution:
Customer Contacts for external analog input control signal.
TB1-11 = COM / Neutral
TB1-12 = AI3 Signal wire (programmable for 0-10, factory set for 4-20ma)
Program under : Complete Settings > Inputs/Outputs > AI/AQ tab > AI3 Configuration
Wiring remote speed reference for an ATV660.
Product Line:
ATV660
Environment:
ALL
Cause:
Wiring / Programming
Resolution:
Customer Contacts for external analog input control signal.
TB1-11 = COM / Neutral
TB1-12 = AI3 Signal wire (programmable for 0-10, factory set for 4-20ma)
Program under : Complete Settings > Inputs/Outputs > AI/AQ tab > AI3 Configuration
Released for: Schneider Electric UK
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Centre
Find support resources for all your needs, in one place.