What is the default IP address of a Premium PLC or ETY Ethernet module?

Article available in these languages: Japanese

Issue:
Default IP address of a Premium PLC or ETY Ethernet module


Product Line:
Premium PLC


Resolution:
The ETY port on the processor or ETY module has a default IP address which is derived from the last 2 octets of the MAC address. The first 2 octets are fixed at 85.16.x.x ;  where x.x is the last 2 octets of the MAC address. For example, If the MAC address is 00.80.F4.02.EA.6A then the IP address will be 85.16.234.106
EA Hex = 234 Decimal
6A Hex = 106 Decimal