Our Brands

Welcome to the Schneider Electric Website

Welcome to our website.
		
How can we help you today?
Can the Vario switch be extended by an Auxiliary contact in ATV650D30N4?
Yes, it is possible.
ATV650, size B (30kW-45kW) has free space on the sides (42mm on left side and more than 100mm on right side).
This ATV size has Vario V5 inside, use aux. block compatible with V5 body.

Schneider Electric UK

Attachment(s)
Vario V5.jpg [58.18 KB]
Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and contact centre
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings