How can we help you today?

What is the error "1031 cannot store the configuration to the device" on SoMove?

Issue:
Error "1031 cannot store the configuration to the device" on SoMove.

Product Line:
Altivar ATV320

Environment:
All serial numbers

Cause:
The error popped up in SoMove when customer tried to download drive program to his PC.

Resolution:
Checked to see customer uses function blocks.  The function blocks can be turned off using SoMove.  In SoMove, go to Parameters in menu bar, click on FULL and select Function Blocks, then under FBCD (FB command) change to "Stop".  Restarted SoMove after the change.

Schneider Electric UK

Explore more

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more

Explore more

Need help?

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Start your sales inquiry online and an expert will connect with you.

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Centre

Find support resources for all your needs, in one place.