How can we help you today?

How do I setup Clock synchronization between the HMISTU and a M221?

Issue:

How do I setup Clock synchronization between the HMISTU and a M221?

Product Line:

Clock synchronization between the HMISTU and a M221

Resolution:

In Vijeo Designer select the target properties and under Startup Options enable Time Management and set Type to PLC Dialog Table.

Please see attachment for more information.

If this FAQ did not solve your issue, you can chat with us at chat with us or e-mail us at customer.services@se.com to create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance:

Support | Schneider Electric Global (se.com)

Schneider Electric UK

Attachment(s)

Explore more

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more

Explore more

Need help?

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Start your sales inquiry online and an expert will connect with you.

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Centre

Find support resources for all your needs, in one place.