Does BMXDAO1615 module have internally connected pins on the module connection?
Issue:
Customer wants to know on BMX DAO1615, any one of the pins between C3/C3, C7/C7, C11/C11, and C15/C15 can be used for the wiring.
Product Line:
x80 DAO module
Environment:
All
Resolution:
Yes. Pins (8,10) C3, Pins (18,20) C7, Pins (28,30) C11 and Pins (38,40) C15 are internally connected.
Customer wants to know on BMX DAO1615, any one of the pins between C3/C3, C7/C7, C11/C11, and C15/C15 can be used for the wiring.
Product Line:
x80 DAO module
Environment:
All
Resolution:
Yes. Pins (8,10) C3, Pins (18,20) C7, Pins (28,30) C11 and Pins (38,40) C15 are internally connected.