What should be done if Ethernet communication for M241/251 logic controllers is interrupted after several hours?

This may come from READ_VAR / WRITE_VAR / READ_WRITE_VAR function blocks being called with an unreachable Server IP address.

For example:

If controller the Ethernet interface settings are:

    • Address: 192.168.0.50
    • Subnet mask: 255.255.255.0
    • Gateway: 0.0.0.0

and the READ_VAR function block tries to communicate with a Server at 192.168.10.20,

Then the Ethernet port may fail after several hours.

Workaround is :

  • Stop trying to reach Server which are not in the same subnet as the controller.
  • Check Ethernet cable status: ETH_R.i_wPortAIpStatus system variable value must be "DATA_EXCHANGE".
  • Use a gateway address (use controller address itself if there is no relevant gateway on the network): requests to unreachable Server will be redirected to the gateway
​