How can we help you today?
What is SSF code on the ATV320 drives?
Issue:
Altivar 320 drive is showing SSF and the motor will not run.
Product line:
Altivar 320, Altivar Machine
Environment:
All model numbers, all serial numbers
Cause:
Torque Limitation
Resolution:
SSF means the drive has reach the Torque Limit fault setting. This parameter is not enabled by default on the drive.
To disable go to CONF > FULL > FLT > TLD > SSD and change the setting to 'no'.
Altivar 320 drive is showing SSF and the motor will not run.
Product line:
Altivar 320, Altivar Machine
Environment:
All model numbers, all serial numbers
Cause:
Torque Limitation
Resolution:
SSF means the drive has reach the Torque Limit fault setting. This parameter is not enabled by default on the drive.
To disable go to CONF > FULL > FLT > TLD > SSD and change the setting to 'no'.
Released for: Schneider Electric UK
Explore more
Range:
Explore more
Range:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Centre
Find support resources for all your needs, in one place.