How can we help you today?
Do any Altivar or Altivar Process AC Drives support AB - DLR Device Level Ring
Issue:
Can the Altivar Process AC Drives support AB - DLR Device Level Ring?
Product Line:
Altivar Process Drive
Resolution:
No Schneider Electric, Altivar AC Drives support Allen Bradley "DLR" Device Level Ring topology.
***
If this article does not answer your question, check out our FAQ database that has answers to more commonly asked questions: Frequently Asked Questions - Schneider Electric (se.com)
if this FAQ did not solve your issue, you can call us at 1-888-778-2733 Option 2 and then 4 or e-mail us at drive.products.support@se.com to create a case with our Technical Support Team.
If you are not located in North America, please contact your local Customer Care Center for assistance: Support | Schneider Electric Global (se.com)
Released for: Schneider Electric UK
Explore more
Range:
Explore more
Range:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Centre
Find support resources for all your needs, in one place.