Our Brands

Welcome to the Schneider Electric Website

Welcome to our website.
		
How can we help you today?
Is is possible to use electronic thermal overload relay between Altistart ATS22 or ATS480 or ATS490 or ATS430 and the motor if there are 2 motors in parallel connected to one Altistart?

Yes, it is possible to use LR9D or LR9F electronic relays due to fact that the current has line frequency (50 or 60Hz)

Schneider Electric UK

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and contact centre
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings