How can we help you today?
How can I set up VIA (0-10Vdc) speed reference on the ATV212 with 70Hz as max speed?
Issue:
Use 0-10Vdc on VIA scaled at 0-70Hz.
Product Line:
ATV212
Environment:
All serial numbers
Cause:
Customer wanted to set 70Hz as max frequency using VIA (0-10Vdc).
Resolution:
In order for the drive to run up to 70Hz using VIA (0-10Vdc) signal, the drive needs to be programmed as follow:
FMOD = 1
FH = 70
UL = 70
F201 = 0
F202 = 0
F203 = 100
F204 = 70
Set the SW100 DIP switch for VIA to the left.
Released for: Schneider Electric UK
Explore more
Range:
Explore more
Range:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Centre
Find support resources for all your needs, in one place.