How can we help you today?
PME 9.0 - Cannot deactivate alarms in Management Console if logged in as a non-admin domain Windows users
Issue
Try to use Management Console's "Deactivate Alarms" feature, as a non-admin user, to deactivate one or more of those active alarms and the following error will appear:
"an unexpected condition was encountered while initializing the AlarmInactivator: Write to Primary data queue failed.."
Product Line
Power Monitoring Expert 9.0
Envorinment
Management Console - "Deactivate Alarm" feature
Cause
PME's MQ setup uses the "Everyone" bucket for permissions and permissions set for the "Everyone" group DO NOT APPLY to domain users by default.
Resolution
Resolution 1:
Run Management Console "As Administrator" (i.e. the right-click menu in Windows).
Resolution 2:
1. Log in as administrator of the server
2. Open the Windows Start menu and search "Computer Management"
3. Open Computer Management then expand Services and Applications > Message Queues
4. Check permissions for all of the private queues by right-clicking on each of them and selecting Properties > Security
- List of private queues to check:
- cloudagent_control
- cloudagent_data
- logsubsystemprimaryrouter_control
- logsubsystemprimaryrouter_data
- logsubsystemsecondaryrouter_control
- logsubsystemsecondaryrouter_data
- Make sure each of the queues listed above have the following permissions:
- "Everyone" group has access to allow:
- Get Properties
- Get Permissions
- Send Message
- "Administrators" group should have full access to the queue
- "ANONYMOUS LOGON" Group should only have access to:
- Send Message
- "Everyone" group has access to allow:
- Get Properties
- Get Permissions
- Send Message
Released for: Schneider Electric UK
Explore more
Range:
Explore more
Range:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Centre
Find support resources for all your needs, in one place.