How can we help you today?
PME 9.0 - New 3rd party device created with DTE does not work
Product Line
Power Monitoring Expert 9.0
Environment
DTE - Device Type Editor
Issue
The new devices created with DTE are not loading and you will see error messages in the System Log:
"Translator map file 'DEVICE_NAME.xml' not loaded due to previous error. Will retry."
"The attribute 'TimestampedByPlugin' on this element is not defined in the DTD/Schema." - (or some other attribute as well)
Cause
The modbus-schema.xml file in the config/translator folder is an old version and does not contain the specific attribute referred by the error log.
Resolution
Replace the modbus-schema.xml file in config/translator with the one from system/translator folder or from a healthy PME system.
Power Monitoring Expert 9.0
Environment
DTE - Device Type Editor
Issue
The new devices created with DTE are not loading and you will see error messages in the System Log:
"Translator map file 'DEVICE_NAME.xml' not loaded due to previous error. Will retry."
"The attribute 'TimestampedByPlugin' on this element is not defined in the DTD/Schema." - (or some other attribute as well)
Cause
The modbus-schema.xml file in the config/translator folder is an old version and does not contain the specific attribute referred by the error log.
Resolution
Replace the modbus-schema.xml file in config/translator with the one from system/translator folder or from a healthy PME system.
Released for: Schneider Electric UK
Explore more
Range:
Explore more
Range:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Centre
Find support resources for all your needs, in one place.