How do you program an ATV320 to stop with a freewheel stop rather than ramp stop?
Issue:
Programming ATV320 to coast to stop rather than a controlled stop
Resolution:
ATV320 default stop is ramp stop. When you need the motor to coast to stop instead of ramp stop, adjust parameters as follows. Navigate on the display to ConF > FULL > Fun > Stt- > Stt. The factory setting is rMP, change this to nSt.