Magelis shows error "configuration file is not unicode"

Issue:
The Magelis HMI fails to boot properly and there is an application halt. The error on the dialog states the following:

Config problem:the configuration file is not unicode
KAOScore:PortableProjectConfiguration.cpp:line 406


Product Line:
Magelis HMI programmed Vijeo Designer (any version)

Resolution:
This error is a result of a corrupt Vijeo Designer installation on the PC where the software is installed. To resolve this issue, please re-install Vijeo Designer and re-download to the HMI.

If this FAQ did not solve your issue, you can chat with us at chat with us or e-mail us at customer.services@se.com to create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance:

Support | Schneider Electric Global (se.com)