On an ATV320, is there a better way to alleviate motor stalling other than adjusting IR compensation?
Issue:
ATV320 alleviating motor stalling options other than adjusting IR compensation
Product Line:
Altivar 320
Environment:
All
Cause:
Motor stalling
Resolution:
You can adjust the speed loop by setting SPGU parameter when CTT=Standard.
Otherwise, set SPG and SIT parameters when CTT=SVCV.
ATV320 alleviating motor stalling options other than adjusting IR compensation
Product Line:
Altivar 320
Environment:
All
Cause:
Motor stalling
Resolution:
You can adjust the speed loop by setting SPGU parameter when CTT=Standard.
Otherwise, set SPG and SIT parameters when CTT=SVCV.