What is the outgoing email address of a PM5500 meter?
Issue
The outgoing email address of the meter needs to be white-listed on the network in order to have security access to send emails.
Product Line
PM5500
Environment
Email subscriptions, SMTP server
Cause
The network firewall will not allow the meter's IP address access to the network to send emails, unless the email address is known and can be white-listed.
Resolution
The address that sends out the email is "DoNotReply@SchneiderElectric.com". However, simply white-listing the meter's IP address rather than the generic email address is preferred. With the current firmware version (V2.7.4), the PM5500 does not have a re-configurable email address.
The outgoing email address of the meter needs to be white-listed on the network in order to have security access to send emails.
Product Line
PM5500
Environment
Email subscriptions, SMTP server
Cause
The network firewall will not allow the meter's IP address access to the network to send emails, unless the email address is known and can be white-listed.
Resolution
The address that sends out the email is "DoNotReply@SchneiderElectric.com". However, simply white-listing the meter's IP address rather than the generic email address is preferred. With the current firmware version (V2.7.4), the PM5500 does not have a re-configurable email address.
Released for: Schneider Electric UK
Explore more
Range:
Explore more
Range:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Centre
Find support resources for all your needs, in one place.