Our Brands

Welcome to the Schneider Electric Website

Welcome to our website.
		
How can we help you today?
What does an EEF1 fault on an Altivar Process Drive mean?

Article available in these languages: Spanish

Issue:
Troubleshoot for an EEF1 fault on a Process Drive

Product Line:
Altivar 6xx and 9xx Process Drives

Environment:
All

Cause:
An error of the internal memory of the control block has been detected.

Resolution:
Verify the environment (electromagnetic compatibility).
This detected error requires a power reset. Remove line voltage until the display goes all the way out. Then reapply line voltage.
If cycling line voltage doesn't clear the fault, save your programming in the keypad or SoMove, and perform a factory reset.
After factory reset cycle line voltage again.
If the fault remains, drive replacement is required.

Schneider Electric UK

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and contact centre
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings