Our Brands

Welcome to the Schneider Electric Website

Welcome to our website.
		
How can we help you today?
Why do some old Quantum I/O modules randomly go to fallback mode when communicating with 140CRA31200 (Ethernet) drop head
This is due to the fact that old components used in IO manufactured before 2008 are more stringent in regards to the internal timing specifications with CRA.

As we could not redesign the "old" IO modules that exist in the field already, the correction is applied in the 140CRA31xxxx .

This correction is embedded in PV06 or later versions of 140CRA31xxxxx

Schneider Electric UK

Explore more
Product:
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Product:
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and contact centre
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings