How can we help you today?
Why is ramp stop the only option for the Type of Stop (Stt) on the ATV320 drive?
Issue:
On ATV320 drive, only ramp stop can be assigned to Type of Stop (Stt).
Product line:
ATV320
Environment:
All serial numbers
Cause:
Customer wanted to assign Freewheel Stop.
Resolution:
If the brake logic function (bLC) has been enabled or if Low speed time out (tLS) is not 0, then the Type of Stop (Stt) parameter is forced to Ramp Stop..
Released for: Schneider Electric UK
Explore more
Range:
Explore more
Range:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Centre
Find support resources for all your needs, in one place.