StruxureWare Data Center Expert report run on web page shows "No Sensor History Available".
Issue:
StruxureWare Data Center Expert report run on web page shows "No Sensor History Available".
Product Line:
StruxureWare Data Center Expert (DCE)
Environment:
DCE version 7.7.1
Cause:
When creating a report / graph on the DCE 7.7.1 web page, you may see the resulting page states "No Sensor History Available". If you run the same report in the Windows Thick client application, you can see that there is indeed data and the report is available.
Resolution:
An upgrade to Data Center Expert 7.8.0 or higher is required to resolve the issue. Please contact you local technical support.
StruxureWare Data Center Expert report run on web page shows "No Sensor History Available".
Product Line:
StruxureWare Data Center Expert (DCE)
Environment:
DCE version 7.7.1
Cause:
When creating a report / graph on the DCE 7.7.1 web page, you may see the resulting page states "No Sensor History Available". If you run the same report in the Windows Thick client application, you can see that there is indeed data and the report is available.
Resolution:
An upgrade to Data Center Expert 7.8.0 or higher is required to resolve the issue. Please contact you local technical support.
Released for: Schneider Electric UK
Explore more
Range:
Explore more
Range:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Centre
Find support resources for all your needs, in one place.