How can we help you today?
ION7650/7550 with current probe phase angle for current does not change after applying calibration constants
Issue
After changing the calibration constants of the current probe in the ION meter using terminal access and command kctstp, the meter's phase angle for current does not change
Product
ION 7650
ION 7550
Environment
ION Setup
Front panel
Power Monitoring Expert
Cause
The phase angle correction is only applied to the kW, kVA, kVAR in the power meter module only
Resolution
Phase angle adjustments are used for power correction only.
After changing the calibration constants of the current probe in the ION meter using terminal access and command kctstp, the meter's phase angle for current does not change
Product
ION 7650
ION 7550
Environment
ION Setup
Front panel
Power Monitoring Expert
Cause
The phase angle correction is only applied to the kW, kVA, kVAR in the power meter module only
Resolution
Phase angle adjustments are used for power correction only.
Released for: Schneider Electric UK
Explore more
Range:
Explore more
Range:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Centre
Find support resources for all your needs, in one place.