How to configure Linux Based Operating Systems for Graceful Shutdown of KVM guest OSs
Issue:
In Linux-based operating systems, the KVM guests do not shut down gracefully when initiating a host OS shutdown.
Product Line:
PowerChute Network Shutdown (PCNS), PowerChute Serial Shutdown (PCSS), and PowerChute Business Edition (PCBE).
Environment:
Linux-based operating systems with KVM enabled (virtual machine installed).
Symptoms:
The KVM Guests are not shutting down gracefully with PCNS, PCSS & PCBE
Resolution:
Resolution:
- Open Terminal in the Linux Host OS and Navigate to /etc/sysconfig/libvirt-guests file
- Uncomment and edit the lines as shown below. Use ‘vi’ command.
ON_BOOT=start
ON_SHUTDOWN=shutdown
SHUTDOWN_TIMEOUT=300
Note: If the libvirt-guests file is not available under /etc/sysconfig
- Create the new file using “ sudo nano /etc/sysconfig/ libvirt-guests “and add the lines below, and save the file.
ON_BOOT=start
ON_SHUTDOWN=shutdown
SHUTDOWN_TIMEOUT=300
- Install the libvirt / libvirt-daemon package using the command below.
- sudo dnf install libvirt libvirt-daemon
- Verify that the qemu-kvm package is installed. If it is not installed, install it using the command below.
- sudo dnf install qemu-kvm
- Enable and start the libvirtd and libvirt-guests service with the following commands.
- systemctl enable libvirtd (To enable the libvirtd service).
- systemctl start libvirtd (To start the libvirtd service).
- systemctl enable libvirt-guests (To enable the libvirt-guests service).
- systemctl start libvirt-guests (To start the libvirt-guests service).
- Reboot the operating system to ensure that the configuration changes are applied.
Released for: Schneider Electric UK
Explore more
Range:
Explore more
Range:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Centre
Find support resources for all your needs, in one place.