How can we help you today?

Modicon M221 - TM3 bus doesn’t work with TM3DM24R or TM3XTYS4 SV 2.0

  • Problem description:
If TM3DM24R or TM3XTYS4 module is placed before TM3 analog input modules (TM3A* or TM3T*) with TM221 controller.
  • Results:
- The TM3 expansion bus communication is not operationnal, the IO ERR Led is fixed red.
- The system word %SW118 is different than 16#FFFF (bit 13 or bit 14 is set to 0).

=> This issue is fixed by the M221 firmware version v1.10.1.3 attached to this FAQ.
  • How to update M221 with .mfw file:
See attached document.

Schneider Electric UK

Attachment(s)
M221 - FW V1.10.1.3.zip [429.2 KB]
How to update M221 with .mfw file.docx.zip [126.12 KB]
Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and contact centre
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • General Terms of Business
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings
  • Preference Center