Our Brands

Welcome to the Schneider Electric Website

Welcome to our website.
		
How can we help you today?
How do I program the ATV320 for remote HMI control?
Issue:
Programming the ATV320 for remote HMI control.

Product line:
ATV320, ATV31 , ATV312

Environment:
All serial numbers

Cause:
Customer would like to control with VW3A1101

Resolution:
Set Ref 1B switching to Ref 1 ch
Set Ref 1 ch to HMI
Set Porfile (CHCF)  to SEP
Set Cmd switching (CCS) to Cd1
Set Cmd cd1 to HMI

Schneider Electric UK

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and contact centre
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings